All Categories
Range TeSys Deca Product Name TeSys GV2 TeSys Deca Product Or Component Type Motor circuit breaker Device Short Name GV2ME Device Application Motor protection Trip Unit Technology Thermal-magnetic
Poles Description 3P Network Type AC Utilisation Category Category A conforming to IEC 60947-2 AC-3 conforming to IEC 60947-4-1 AC-3e conforming to IEC 60947-4-1 Network Frequency 50/60 Hz conforming to IEC 60947-4-1 Fixing Mode 35 mm symmetrical DIN rail: clipped Panel: screwed (with adaptor plate) Motor Power Kw 0.37 kW at 400/415 V AC 50/60 Hz 0.55 kW at 400/415 V AC 50/60 Hz 0.37 kW at 500 V AC 50/60 Hz 0.55 kW at 500 V AC 50/60 Hz 0.75 kW at 500 V AC 50/60 Hz 0.75 kW at 690 V AC 50/60 Hz 1.1 kW at 690 V AC 50/60 Hz
Breaking Capacity 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 [Ics] Rated Service Short-Circuit Breaking Capacity 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2
Control Type Push-button [In] Rated Current 1.6 A Thermal Protection Adjustment Range 1…1.6 A conforming to IEC 60947-4-1 Magnetic Tripping Current 22.5 A [Ith] Conventional Free Air Thermal Current 1.6 A conforming to IEC 60947-4-1 [Ue] Rated Operational Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2
[Ui] Rated Insulation Voltage 690 V AC 50/60 Hz conforming to IEC 60947-2 [Uimp] Rated Impulse Withstand Voltage 6 kV conforming to IEC 60947-2 Phase Failure Sensitivity Yes conforming to IEC 60947-4-1 Suitability For Isolation Yes conforming to IEC 60947-1 § 7-1-6 Power Dissipation Per Pole 2.5 W Mechanical Durability 100000 cycles Electrical Durability 100000 cycles for AC-3 at 415 V In 100000 cycles for AC-3e at 415 V In Rated Duty Continuous conforming to IEC 60947-4-1 Tightening Torque 1.7 N.m - on screw clamp terminal Width 45 mm Height 89 mm Depth 78.5 mm Net Weight 0.26 kg Colour Dark grey
GV2ME06 - MPCB - Motor Protection circuit breaker, TeSys GV2, 3P, 1-1.6 A, thermal magnetic, screw clamp terminals